UNPKG

iobroker.enocean

Version:

Connects EnOcean devices via USB/Serial devices with TCM300 Chips

47 lines (46 loc) 1.37 kB
{ "eep": "A5-10-10", "rorg_number": "0xA5", "telegram": "4BS", "func_number": "0x10", "type_number": "0x10", "type_title": "Room Operating Panel Temperature, Humidity, Set Point and Occupancy control", "bidirectional": false, "objects": { "preDefined": ["TMP", "HUM", "SP", "OCC"] }, "case": [{ "send": false, "datafield": [ { "data": "Set point", "shortcut": "SP", "bitoffs": "0", "bitsize": "8", "value": {"var": "value"} }, { "data": "Humidity", "shortcut": "HUM", "bitoffs": "8", "bitsize": "8", "value": {"+": [{"*": [{"-": [{"var": "value"}, 0]}, 0.4]}, 0]} }, { "data": "Temperature", "shortcut": "TMP", "bitoffs": "16", "bitsize": "8", "value": {"+": [{"*": [{ "-": [{"var": "value"}, 0] }, 0.156862745]}, 0]}, "decimals": 2 }, { "data": "Occupancy", "shortcut": "OCC", "bitoffs": "31", "bitsize": "1", "value": {"==": [{"var": "value"}, 0]} } ] }] }