Title Register type Register Division factor Unit Size of variable Min value Max value Default value
Current outdoor temperature (BT1) MODBUS_INPUT_REGISTER 1 10 °C s16 0 0 0
Supply line (EP23-BT2) MODBUS_INPUT_REGISTER 2 10 °C s16 0 0 0
Supply line (EP22-BT2) MODBUS_INPUT_REGISTER 3 10 °C s16 0 0 0
Supply line (EP21-BT2) MODBUS_INPUT_REGISTER 4 10 °C s16 0 0 0
Supply line (BT2) MODBUS_INPUT_REGISTER 5 10 °C s16 0 0 0
Return line (BT3) MODBUS_INPUT_REGISTER 7 10 °C s16 0 0 0
Hot water charging (BT6) MODBUS_INPUT_REGISTER 9 10 °C s16 0 0 0
Brine in (BT10) MODBUS_INPUT_REGISTER 10 10 °C s16 0 0 0
Brine out (BT11) MODBUS_INPUT_REGISTER 11 10 °C s16 0 0 0
Condenser sensor supply line (BT12) MODBUS_INPUT_REGISTER 12 10 °C s16 0 0 0
Discharge (BT14) MODBUS_INPUT_REGISTER 13 10 °C s16 0 0 0
Liquid line (BT15) MODBUS_INPUT_REGISTER 14 10 °C s16 0 0 0
Suction gas (BT17) MODBUS_INPUT_REGISTER 16 10 °C s16 0 0 0
Collector in (AZ10-BT26) MODBUS_INPUT_REGISTER 21 10 °C s16 0 0 0
Collector out (AZ10-BT27) MODBUS_INPUT_REGISTER 22 10 °C s16 0 0 0
Roomsensor 3-1 MODBUS_INPUT_REGISTER 24 10 °C s16 0 0 0
Roomsensor 2-1 MODBUS_INPUT_REGISTER 25 10 °C s16 0 0 0
Return line (EQ1-BT65) MODBUS_INPUT_REGISTER 31 10 °C s16 0 0 0
Temperature limiter (EB100-FD1) MODBUS_INPUT_REGISTER 36 1 s16 0 0 0
Average temperature (BT1) MODBUS_INPUT_REGISTER 37 10 °C s16 0 0 0
Boiler temperature (BT52) MODBUS_INPUT_REGISTER 38 10 °C s16 0 0 0
External supply line (BT25) MODBUS_INPUT_REGISTER 39 10 °C s16 0 0 0
Flow sensor (BF1) MODBUS_INPUT_REGISTER 40 10 l/min s16 0 0 0
Electrical anode (EB100-FR1) MODBUS_INPUT_REGISTER 41 1 s16 0 0 0
Pool (CL12-BT51) MODBUS_INPUT_REGISTER 59 10 °C s16 0 0 0
Collector in (AZ13-BT26) MODBUS_INPUT_REGISTER 66 10 °C s16 0 0 0
Collector in (AZ12-BT26) MODBUS_INPUT_REGISTER 67 10 °C s16 0 0 0
Collector in (AZ11-BT26) MODBUS_INPUT_REGISTER 68 10 °C s16 0 0 0
Collector out (AZ13-BT27) MODBUS_INPUT_REGISTER 69 10 °C s16 0 0 0
Collector out (AZ12-BT27) MODBUS_INPUT_REGISTER 70 10 °C s16 0 0 0
Collector out (AZ11-BT27) MODBUS_INPUT_REGISTER 71 10 °C s16 0 0 0
Return line (EP23-BT3) MODBUS_INPUT_REGISTER 75 10 °C s16 0 0 0
Return line (EP22-BT3) MODBUS_INPUT_REGISTER 76 10 °C s16 0 0 0
Return line (EP21-BT3) MODBUS_INPUT_REGISTER 77 10 °C s16 0 0 0
Return line (EP15-BT3) MODBUS_INPUT_REGISTER 78 10 °C s16 0 0 0
Outgoing hot water (BT70) MODBUS_INPUT_REGISTER 87 10 °C s16 0 0 0
Collector (EQ1-BT57) MODBUS_INPUT_REGISTER 90 10 °C s16 0 0 0
Heating dump (EQ1-BT75) MODBUS_INPUT_REGISTER 91 10 °C s16 0 0 0
Supply line (EP47-BT2) MODBUS_INPUT_REGISTER 94 10 °C s16 0 0 0
Supply line (EP46-BT2) MODBUS_INPUT_REGISTER 95 10 °C s16 0 0 0
Supply line (EP45-BT2) MODBUS_INPUT_REGISTER 96 10 °C s16 0 0 0
Supply line (EP44-BT2) MODBUS_INPUT_REGISTER 97 10 °C s16 0 0 0
Return line (EP47-BT3) MODBUS_INPUT_REGISTER 98 10 °C s16 0 0 0
Return line (EP46-BT3) MODBUS_INPUT_REGISTER 99 10 °C s16 0 0 0
Return line (EP45-BT3) MODBUS_INPUT_REGISTER 100 10 °C s16 0 0 0
Return line (EP44-BT3) MODBUS_INPUT_REGISTER 101 10 °C s16 0 0 0
Brine in (EP10-BT26) MODBUS_INPUT_REGISTER 106 10 °C s16 0 0 0
Room average temp. clim. system 8 (BT50) MODBUS_INPUT_REGISTER 109 10 °C s16 0 0 0
Room average temp. clim. system 7 (BT50) MODBUS_INPUT_REGISTER 110 10 °C s16 0 0 0
Room average temp. clim. system 6 (BT50) MODBUS_INPUT_REGISTER 111 10 °C s16 0 0 0
Room average temp. clim. system 5 (BT50) MODBUS_INPUT_REGISTER 112 10 °C s16 0 0 0
Room average temp. clim. system 4 (BT50) MODBUS_INPUT_REGISTER 113 10 °C s16 0 0 0
Room average temp. clim. system 3 (BT50) MODBUS_INPUT_REGISTER 114 10 °C s16 0 0 0
Room average temp. clim. system 2 (BT50) MODBUS_INPUT_REGISTER 115 10 °C s16 0 0 0
Room average temp. clim. system 1 (BT50) MODBUS_INPUT_REGISTER 116 10 °C s16 0 0 0
Oper. mode shunt climate system 8 MODBUS_INPUT_REGISTER 129 1 u8 0 0 0
Oper. mode shunt climate system 7 MODBUS_INPUT_REGISTER 130 1 u8 0 0 0
Oper. mode shunt climate system 6 MODBUS_INPUT_REGISTER 131 1 u8 0 0 0
Oper. mode shunt climate system 5 MODBUS_INPUT_REGISTER 132 1 u8 0 0 0
Relay status (ERS 1) MODBUS_INPUT_REGISTER 134 1 u8 0 0 0
Fan speed (AZ30-GQ2) MODBUS_INPUT_REGISTER 135 1 % u8 0 0 0
Fan speed (AZ30-GQ3) MODBUS_INPUT_REGISTER 136 1 % u8 0 0 0
Current hot water mode controlled by MODBUS_INPUT_REGISTER 137 1 s8 0 0 0
Inverter limit status MODBUS_INPUT_REGISTER 138 1 u8 0 0 0
Inverter fault reset MODBUS_HOLDING_REGISTER 2755 1 u16 1 1 1
Requested compressor frequency MODBUS_INPUT_REGISTER 140 1 Hz u16 0 0 0
Max. compressor frequency, heating MODBUS_INPUT_REGISTER 141 100 Hz u16 0 0 0
Inverter alarm code MODBUS_INPUT_REGISTER 142 1 u16 0 0 0
Inverter fault code MODBUS_INPUT_REGISTER 143 1 u16 0 0 0
Inverter run command MODBUS_INPUT_REGISTER 144 1 u16 0 0 0
Inverter pic. version MODBUS_INPUT_REGISTER 145 1 u16 0 0 0
Inverter 8051 version MODBUS_INPUT_REGISTER 146 1 u16 0 0 0
Inverter wizard MODBUS_INPUT_REGISTER 147 1 u16 0 0 0
Inverter version (MCE) MODBUS_INPUT_REGISTER 148 1 u16 0 0 0
Inverter hw version MODBUS_INPUT_REGISTER 149 1 u16 0 0 0
Inverter hw type MODBUS_INPUT_REGISTER 150 1 u16 0 0 0
External adjustment climate system 8 MODBUS_INPUT_REGISTER 151 1 u8 0 0 0
External adjustment climate system 7 MODBUS_INPUT_REGISTER 152 1 u8 0 0 0
External adjustment climate system 6 MODBUS_INPUT_REGISTER 153 1 u8 0 0 0
External adjustment climate system 5 MODBUS_INPUT_REGISTER 154 1 u8 0 0 0
Climate system 8 MODBUS_INPUT_REGISTER 156 1 u8 0 0 0
Climate system 7 MODBUS_INPUT_REGISTER 157 1 u8 0 0 0
Climate system 6 MODBUS_INPUT_REGISTER 158 1 u8 0 0 0
Climate system 5 MODBUS_INPUT_REGISTER 159 1 u8 0 0 0
Extra cooling MODBUS_INPUT_REGISTER 160 1 u8 0 0 0
Hot water comfort return (BT82) MODBUS_INPUT_REGISTER 174 10 °C s16 0 0 0
Hot water comfort heater (BT83) MODBUS_INPUT_REGISTER 175 10 °C s16 0 0 0
Compressor, total time pool, heat pump 8 (EP15) MODBUS_INPUT_REGISTER 179 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 8 (EP15) MODBUS_INPUT_REGISTER 181 1 h u32 0 0 0
Compressor, total time pool, heat pump 8 (EP14) MODBUS_INPUT_REGISTER 185 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 8 (EP14) MODBUS_INPUT_REGISTER 187 1 h u32 0 2147483647 0
Compressor, total time pool, heat pump 7 (EP15) MODBUS_INPUT_REGISTER 191 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 7 (EP15) MODBUS_INPUT_REGISTER 193 1 h u32 0 0 0
Compressor, total time pool, heat pump 7 (EP14) MODBUS_INPUT_REGISTER 197 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 7 (EP14) MODBUS_INPUT_REGISTER 199 1 h u32 0 2147483647 0
Compressor, total time pool, heat pump 6 (EP15) MODBUS_INPUT_REGISTER 203 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 6 (EP15) MODBUS_INPUT_REGISTER 205 1 h u32 0 0 0
Compressor, total time pool, heat pump 6 (EP14) MODBUS_INPUT_REGISTER 209 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 6 (EP14) MODBUS_INPUT_REGISTER 211 1 h u32 0 2147483647 0
Compressor, total time pool, heat pump 5 (EP15) MODBUS_INPUT_REGISTER 215 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 5 (EP15) MODBUS_INPUT_REGISTER 217 1 h u32 0 0 0
Compressor, total time pool, heat pump 5 (EP14) MODBUS_INPUT_REGISTER 221 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 5 (EP14) MODBUS_INPUT_REGISTER 223 1 h u32 0 2147483647 0
Compressor, total time pool, heat pump 4 (EP15) MODBUS_INPUT_REGISTER 227 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 4 (EP15) MODBUS_INPUT_REGISTER 229 1 h u32 0 0 0
Compressor, total time pool, heat pump 4 (EP14) MODBUS_INPUT_REGISTER 233 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 4 (EP14) MODBUS_INPUT_REGISTER 235 1 h u32 0 2147483647 0
Compressor, total time pool, heat pump 3 (EP15) MODBUS_INPUT_REGISTER 239 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 3 (EP15) MODBUS_INPUT_REGISTER 241 1 h u32 0 0 0
Compressor, total time pool, heat pump 3 (EP14) MODBUS_INPUT_REGISTER 245 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 3 (EP14) MODBUS_INPUT_REGISTER 247 1 h u32 0 2147483647 0
Compressor, total time pool, heat pump 2 (EP15) MODBUS_INPUT_REGISTER 251 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 2 (EP15) MODBUS_INPUT_REGISTER 253 1 h u32 0 0 0
Compressor, total time pool, heat pump 2 (EP14) MODBUS_INPUT_REGISTER 257 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 2 (EP14) MODBUS_INPUT_REGISTER 259 1 h u32 0 2147483647 0
Compressor, total time pool, heat pump 1 (EP15) MODBUS_INPUT_REGISTER 263 1 h u32 0 0 0
Compressor, total time pool 2, heat pump 1 (EP15) MODBUS_INPUT_REGISTER 265 1 h u32 0 0 0
Compressor, total time pool, heat pump 1 (EP14) MODBUS_INPUT_REGISTER 269 1 h u32 0 2147483647 0
Compressor, total time pool 2, heat pump 1 (EP14) MODBUS_INPUT_REGISTER 271 1 h u32 0 2147483647 0
Total run time compressor cooling MODBUS_INPUT_REGISTER 279 1 h u32 0 2147483647 0
Compressor, total time pool, main unit (EP14) MODBUS_INPUT_REGISTER 281 1 h u32 0 2147483647 0
Compressor, total time pool 2, main unit (EP14) MODBUS_INPUT_REGISTER 283 1 h u32 0 2147483647 0
Heat pump 8 requested compressor frequency MODBUS_INPUT_REGISTER 294 1 Hz u8 0 0 0
Heat pump 7 requested compressor frequency MODBUS_INPUT_REGISTER 295 1 Hz u8 0 0 0
Heat pump 6 requested compressor frequency MODBUS_INPUT_REGISTER 296 1 Hz u8 0 0 0
Heat pump 5 requested compressor frequency MODBUS_INPUT_REGISTER 297 1 Hz u8 0 0 0
Heat pump 4 requested compressor frequency MODBUS_INPUT_REGISTER 298 1 Hz u8 0 0 0
Heat pump 3 requested compressor frequency MODBUS_INPUT_REGISTER 299 1 Hz u8 0 0 0
Heat pump 2 requested compressor frequency MODBUS_INPUT_REGISTER 300 1 Hz u8 0 0 0
Heat pump 1 requested compressor frequency MODBUS_INPUT_REGISTER 301 1 Hz u8 0 0 0
Frost protection heat exchanger heat pump 8 MODBUS_INPUT_REGISTER 303 1 u8 0 0 0
Frost protection heat exchanger heat pump 7 MODBUS_INPUT_REGISTER 304 1 u8 0 0 0
Frost protection heat exchanger heat pump 6 MODBUS_INPUT_REGISTER 305 1 u8 0 0 0
Frost protection heat exchanger heat pump 5 MODBUS_INPUT_REGISTER 306 1 u8 0 0 0
Frost protection heat exchanger heat pump 4 MODBUS_INPUT_REGISTER 307 1 u8 0 0 0
Frost protection heat exchanger heat pump 3 MODBUS_INPUT_REGISTER 308 1 u8 0 0 0
Frost protection heat exchanger heat pump 2 MODBUS_INPUT_REGISTER 309 1 u8 0 0 0
Compressor restrictions MODBUS_INPUT_REGISTER 2021 1 u32 0 0 0
Available compressors heating MODBUS_INPUT_REGISTER 317 1 u8 0 0 0
Available compressors hot water MODBUS_INPUT_REGISTER 318 1 u8 0 0 0
Available compressors pool 1 MODBUS_INPUT_REGISTER 319 1 u8 0 0 0
Available compressors pool 2 MODBUS_INPUT_REGISTER 320 1 u8 0 0 0
Available compressors cooling MODBUS_INPUT_REGISTER 321 1 u8 0 0 0
Available compressors external control MODBUS_INPUT_REGISTER 322 1 u8 0 0 0
Supply temperature (BT64) MODBUS_INPUT_REGISTER 337 10 °C s16 0 0 0
Heat pump functionality 2 MODBUS_INPUT_REGISTER 338 1 u32 0 0 0
Status (EQ1) MODBUS_INPUT_REGISTER 340 1 u8 0 0 0
Status, heating dump shunt (EQ1) MODBUS_INPUT_REGISTER 341 1 u8 0 0 0
Degree minutes MODBUS_HOLDING_REGISTER 11 10 DM s32 -30000 30000 0
Blocking (ERS 1) MODBUS_INPUT_REGISTER 358 1 u8 0 0 0
AZ30-EB17 MODBUS_INPUT_REGISTER 359 1 u8 0 0 0
Seconds of blank time left, charge pump 8 MODBUS_INPUT_REGISTER 385 1 u8 0 0 0
Seconds of blank time left, charge pump 7 MODBUS_INPUT_REGISTER 386 1 u8 0 0 0
Seconds of blank time left, charge pump 6 MODBUS_INPUT_REGISTER 387 1 u8 0 0 0
Seconds of blank time left, charge pump 5 MODBUS_INPUT_REGISTER 388 1 u8 0 0 0
Seconds of blank time left, charge pump 4 MODBUS_INPUT_REGISTER 389 1 u8 0 0 0
Seconds of blank time left, charge pump 3 MODBUS_INPUT_REGISTER 390 1 u8 0 0 0
Seconds of blank time left, charge pump 2 MODBUS_INPUT_REGISTER 391 1 u8 0 0 0
Seconds of blank time left, charge pump 1 MODBUS_INPUT_REGISTER 392 1 u8 0 0 0
Inverter min speed MODBUS_INPUT_REGISTER 394 1 u16 0 0 0
Inverter max speed MODBUS_INPUT_REGISTER 395 1 u16 0 0 0
Pulse energy meter (BE6) MODBUS_INPUT_REGISTER 398 100 kWh u32 0 2147483647 0
Max fan speed (EB101) MODBUS_INPUT_REGISTER 402 1 rpm u16 0 0 0
Min fan speed (EB101) MODBUS_INPUT_REGISTER 403 1 rpm u16 0 0 0
Generated power heating (EB101) MODBUS_INPUT_REGISTER 406 10 kW u16 0 0 0
Time to defrosting (EB101) MODBUS_INPUT_REGISTER 407 1 min u16 0 0 0
Defrosting index (EB101) MODBUS_INPUT_REGISTER 408 1 u16 0 0 0
Superheat reference EEV (EB101) MODBUS_INPUT_REGISTER 409 10 °C s16 0 0 0
Superheat EEV (EB101) MODBUS_INPUT_REGISTER 410 10 °C s16 0 0 0
EEV-ssh-error (EB101) MODBUS_INPUT_REGISTER 411 10 °C s16 0 0 0
Superheat temp. reference EEV (EB101) MODBUS_INPUT_REGISTER 412 10 °C s16 0 0 0
Set point value EEV (EB101) MODBUS_INPUT_REGISTER 413 10 °C s16 0 0 0
EEV PV (EB101) MODBUS_INPUT_REGISTER 414 10 °C s16 0 0 0
EEV-te-error average open (EB101) MODBUS_INPUT_REGISTER 415 10 °C s16 0 0 0
Degree of opening EEV (EB101) MODBUS_INPUT_REGISTER 416 1 u16 0 0 0
Superheat reference EVI (EB101) MODBUS_INPUT_REGISTER 417 10 °C s16 0 0 0
Superheat EVI (EB101) MODBUS_INPUT_REGISTER 418 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB101) MODBUS_INPUT_REGISTER 419 10 °C s16 0 0 0
Superheat temp. reference EVI (EB101) MODBUS_INPUT_REGISTER 420 10 °C s16 0 0 0
Set point value EVI (EB101) MODBUS_INPUT_REGISTER 421 10 °C s16 0 0 0
EVI PV (EB101) MODBUS_INPUT_REGISTER 422 10 °C s16 0 0 0
EEV-te-error average open in (EVI)(EB101) MODBUS_INPUT_REGISTER 423 10 °C s16 0 0 0
Degree of opening EVI (EB101) MODBUS_INPUT_REGISTER 424 1 u16 0 0 0
Low press (EB108 BP8 dew) MODBUS_INPUT_REGISTER 438 10 °C s16 0 0 0
Hi press (EB108 BP9 dew) MODBUS_INPUT_REGISTER 439 10 °C s16 0 0 0
EVI pressure (EB108-EP14-BP11 dew) MODBUS_INPUT_REGISTER 442 10 °C s16 0 0 0
Fan status (EB108-EP14) MODBUS_INPUT_REGISTER 444 1 u8 0 0 0
Fan rpm (EB108-EP14) MODBUS_INPUT_REGISTER 445 1 rpm u16 0 0 0
Low press (EB107 BP8 dew) MODBUS_INPUT_REGISTER 454 10 °C s16 0 0 0
Hi press (EB107 BP9 dew) MODBUS_INPUT_REGISTER 455 10 °C s16 0 0 0
EVI pressure (EB107-EP14-BP11 dew) MODBUS_INPUT_REGISTER 458 10 °C s16 0 0 0
Fan status (EB107-EP14) MODBUS_INPUT_REGISTER 460 1 u8 0 0 0
Fan rpm (EB107-EP14) MODBUS_INPUT_REGISTER 461 1 rpm u16 0 0 0
Low press (EB106 BP8 dew) MODBUS_INPUT_REGISTER 470 10 °C s16 0 0 0
Hi press (EB106 BP9 dew) MODBUS_INPUT_REGISTER 471 10 °C s16 0 0 0
EVI pressure (EB106-EP14-BP11 dew) MODBUS_INPUT_REGISTER 474 10 °C s16 0 0 0
Fan status (EB106-EP14) MODBUS_INPUT_REGISTER 476 1 u8 0 0 0
Fan rpm (EB106-EP14) MODBUS_INPUT_REGISTER 477 1 rpm u16 0 0 0
Low press (EB105 BP8 dew) MODBUS_INPUT_REGISTER 486 10 °C s16 0 0 0
Hi press (EB105 BP9 dew) MODBUS_INPUT_REGISTER 487 10 °C s16 0 0 0
EVI pressure (EB105-EP14-BP11 dew) MODBUS_INPUT_REGISTER 490 10 °C s16 0 0 0
Fan status (EB105-EP14) MODBUS_INPUT_REGISTER 492 1 u8 0 0 0
Fan rpm (EB105-EP14) MODBUS_INPUT_REGISTER 493 1 rpm u16 0 0 0
Low press (EB104 BP8 dew) MODBUS_INPUT_REGISTER 502 10 °C s16 0 0 0
Hi press (EB104 BP9 dew) MODBUS_INPUT_REGISTER 503 10 °C s16 0 0 0
EVI pressure (EB104-EP14-BP11 dew) MODBUS_INPUT_REGISTER 506 10 °C s16 0 0 0
Fan status (EB104-EP14) MODBUS_INPUT_REGISTER 508 1 u8 0 0 0
Fan rpm (EB104-EP14) MODBUS_INPUT_REGISTER 509 1 rpm u16 0 0 0
Low press (EB103 BP8 dew) MODBUS_INPUT_REGISTER 518 10 °C s16 0 0 0
Hi press (EB103 BP9 dew) MODBUS_INPUT_REGISTER 519 10 °C s16 0 0 0
EVI pressure (EB103-EP14-BP11 dew) MODBUS_INPUT_REGISTER 522 10 °C s16 0 0 0
Fan status (EB103-EP14) MODBUS_INPUT_REGISTER 524 1 u8 0 0 0
Fan rpm (EB103-EP14) MODBUS_INPUT_REGISTER 525 1 rpm u16 0 0 0
Low press (EB102 BP8 dew) MODBUS_INPUT_REGISTER 534 10 °C s16 0 0 0
Hi press (EB102 BP9 dew) MODBUS_INPUT_REGISTER 535 10 °C s16 0 0 0
EVI pressure (EB102-EP14-BP11 dew) MODBUS_INPUT_REGISTER 538 10 °C s16 0 0 0
Fan status (EB102-EP14) MODBUS_INPUT_REGISTER 540 1 u8 0 0 0
Fan rpm (EB102-EP14) MODBUS_INPUT_REGISTER 541 1 rpm u16 0 0 0
Low press (EB101 BP8 dew) MODBUS_INPUT_REGISTER 550 10 °C s16 0 0 0
Hi press (EB101 BP9 dew) MODBUS_INPUT_REGISTER 551 10 °C s16 0 0 0
EVI pressure (EB101-EP14-BP11 dew) MODBUS_INPUT_REGISTER 554 10 °C s16 0 0 0
Fan status (EB101-EP14) MODBUS_INPUT_REGISTER 556 1 u8 0 0 0
Fan rpm (EB101-EP14) MODBUS_INPUT_REGISTER 557 1 rpm u16 0 0 0
Operating mode PV panels MODBUS_INPUT_REGISTER 579 1 u8 0 0 0
EME lux mode without EME MODBUS_INPUT_REGISTER 581 1 u8 0 0 0
Timer (EME) MODBUS_INPUT_REGISTER 582 60 min u16 0 0 0
Fan mode 4 MODBUS_INPUT_REGISTER 590 1 % u8 0 0 0
Fan mode 3 MODBUS_INPUT_REGISTER 591 1 % u8 0 0 0
Fan mode 2 MODBUS_INPUT_REGISTER 592 1 % u8 0 0 0
Is the compressor accessible MODBUS_INPUT_REGISTER 593 1 u8 0 0 0
Permit (undefined) MODBUS_INPUT_REGISTER 683 1 u8 0 0 0
Permit (undefined) MODBUS_INPUT_REGISTER 684 1 u8 0 0 0
Permit (undefined) MODBUS_INPUT_REGISTER 685 1 u8 0 0 0
Permit (OPT 10) additional heat MODBUS_INPUT_REGISTER 686 1 u8 0 0 0
Permit ext. imm. heater step MODBUS_INPUT_REGISTER 687 1 u8 0 0 0
Permit int. imm. heater step MODBUS_INPUT_REGISTER 688 1 u8 0 0 0
Permit shunted additional heat MODBUS_INPUT_REGISTER 689 1 u8 0 0 0
Permit prioritised additional heat MODBUS_INPUT_REGISTER 690 1 u8 0 0 0
Permit (EB108-EP15) MODBUS_INPUT_REGISTER 691 1 u8 0 0 0
Permit (EB107-EP15) MODBUS_INPUT_REGISTER 692 1 u8 0 0 0
Permit (EB106-EP15) MODBUS_INPUT_REGISTER 693 1 u8 0 0 0
Permit (EB105-EP15) MODBUS_INPUT_REGISTER 694 1 u8 0 0 0
Permit (EB104-EP15) MODBUS_INPUT_REGISTER 695 1 u8 0 0 0
Permit (EB103-EP15) MODBUS_INPUT_REGISTER 696 1 u8 0 0 0
Permit (EB102-EP15) MODBUS_INPUT_REGISTER 697 1 u8 0 0 0
Permit (EB101-EP15) MODBUS_INPUT_REGISTER 698 1 u8 0 0 0
Permit (EB100-EP15) MODBUS_INPUT_REGISTER 699 1 u8 0 0 0
Permit (EB108-EP14) MODBUS_INPUT_REGISTER 700 1 u8 0 0 0
Permit (EB107-EP14) MODBUS_INPUT_REGISTER 701 1 u8 0 0 0
Permit (EB106-EP14) MODBUS_INPUT_REGISTER 702 1 u8 0 0 0
Permit (EB105-EP14) MODBUS_INPUT_REGISTER 703 1 u8 0 0 0
Permit (EB104-EP14) MODBUS_INPUT_REGISTER 704 1 u8 0 0 0
Permit (EB103-EP14) MODBUS_INPUT_REGISTER 705 1 u8 0 0 0
Permit (EB102-EP14) MODBUS_INPUT_REGISTER 706 1 u8 0 0 0
Permit (EB101-EP14) MODBUS_INPUT_REGISTER 707 1 u8 0 0 0
Permit (EB100-EP14) MODBUS_INPUT_REGISTER 708 1 u8 0 0 0
Smart energy source, priority 7, start DM MODBUS_INPUT_REGISTER 709 1 s32 0 0 0
Smart energy source, priority 6, start DM MODBUS_INPUT_REGISTER 711 1 s32 0 0 0
Smart energy source, priority 5, start DM MODBUS_INPUT_REGISTER 713 1 s32 0 0 0
Smart energy source, priority 4, start DM MODBUS_INPUT_REGISTER 715 1 s32 0 0 0
Smart energy source, priority 3, start DM MODBUS_INPUT_REGISTER 717 1 s32 0 0 0
Smart energy source, priority 2, start DM MODBUS_INPUT_REGISTER 719 1 s32 0 0 0
Smart energy source, priority 1, start DM MODBUS_INPUT_REGISTER 721 1 s32 0 0 0
Smart energy source, priority 7, stop DM MODBUS_INPUT_REGISTER 723 1 s32 0 0 0
Smart energy source, priority 6, stop DM MODBUS_INPUT_REGISTER 725 1 s32 0 0 0
Smart energy source, priority 5, stop DM MODBUS_INPUT_REGISTER 727 1 s32 0 0 0
Smart energy source, priority 4, stop DM MODBUS_INPUT_REGISTER 729 1 s32 0 0 0
Smart energy source, priority 3, stop DM MODBUS_INPUT_REGISTER 731 1 s32 0 0 0
Smart energy source, priority 2, stop DM MODBUS_INPUT_REGISTER 733 1 s32 0 0 0
Smart energy source, priority 1, stop DM MODBUS_INPUT_REGISTER 735 1 s32 0 0 0
Smart energy source, DM minimum value MODBUS_INPUT_REGISTER 737 1 s32 0 0 0
External guide status MODBUS_INPUT_REGISTER 745 1 u8 0 0 0
Test guide value MODBUS_INPUT_REGISTER 746 1 u16 0 0 0
Temp. lux forces start of hot water demand MODBUS_INPUT_REGISTER 747 1 u8 0 0 0
Wood boiler activated MODBUS_INPUT_REGISTER 759 1 u8 0 0 0
Max fan speed (EB108-F21x0) MODBUS_INPUT_REGISTER 762 1 rpm u16 0 0 0
Min fan speed (EB108) MODBUS_INPUT_REGISTER 763 1 rpm u16 0 0 0
Generated power heating (EB108) MODBUS_INPUT_REGISTER 766 10 kW u16 0 0 0
Time to defrosting (EB108) MODBUS_INPUT_REGISTER 767 1 min u16 0 0 0
Defrosting index (EB108) MODBUS_INPUT_REGISTER 768 1 u16 0 0 0
Superheat reference EEV (EB108) MODBUS_INPUT_REGISTER 769 10 °C s16 0 0 0
Superheat EEV (EB108) MODBUS_INPUT_REGISTER 770 10 °C s16 0 0 0
EEV-ssh-error (EB108) MODBUS_INPUT_REGISTER 771 10 °C s16 0 0 0
Superheat temp. reference EEV (EB108) MODBUS_INPUT_REGISTER 772 10 °C s16 0 0 0
Set point value EEV (EB108) MODBUS_INPUT_REGISTER 773 10 °C s16 0 0 0
EEV PV (EB108) MODBUS_INPUT_REGISTER 774 10 °C s16 0 0 0
EEV-te-error average open (EB108) MODBUS_INPUT_REGISTER 775 10 °C s16 0 0 0
Degree of opening EEV (EB108) MODBUS_INPUT_REGISTER 776 1 u16 0 0 0
Superheat reference EVI (EB108) MODBUS_INPUT_REGISTER 777 10 °C s16 0 0 0
Superheat EVI (EB108) MODBUS_INPUT_REGISTER 778 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB108) MODBUS_INPUT_REGISTER 779 10 °C s16 0 0 0
Superheat temp. reference EVI (EB108) MODBUS_INPUT_REGISTER 780 10 °C s16 0 0 0
Set point value EVI (EB108) MODBUS_INPUT_REGISTER 781 10 °C s16 0 0 0
EVI PV (EB108) MODBUS_INPUT_REGISTER 782 10 °C s16 0 0 0
EEV-te-error average open (EVI)(EB108) MODBUS_INPUT_REGISTER 783 10 °C s16 0 0 0
Degree of opening EVI (EB108) MODBUS_INPUT_REGISTER 784 1 u16 0 0 0
Max fan speed (EB107) MODBUS_INPUT_REGISTER 787 1 rpm u16 0 0 0
Min fan speed (EB107) MODBUS_INPUT_REGISTER 788 1 rpm u16 0 0 0
Generated power heating (EB107) MODBUS_INPUT_REGISTER 791 10 kW u16 0 0 0
Defrosting index (EB107) MODBUS_INPUT_REGISTER 793 1 u16 0 0 0
Superheat reference EEV (EB107) MODBUS_INPUT_REGISTER 794 10 °C s16 0 0 0
Superheat EEV (EB107) MODBUS_INPUT_REGISTER 795 10 °C s16 0 0 0
EEV-ssh-error (EB107) MODBUS_INPUT_REGISTER 796 10 °C s16 0 0 0
Superheat temp. reference EEV (EB107) MODBUS_INPUT_REGISTER 797 10 °C s16 0 0 0
Set point value EEV (EB107) MODBUS_INPUT_REGISTER 798 10 °C s16 0 0 0
EEV PV (EB107) MODBUS_INPUT_REGISTER 799 10 °C s16 0 0 0
EEV-te-error average open (EB107) MODBUS_INPUT_REGISTER 800 10 °C s16 0 0 0
Degree of opening EEV (EB107) MODBUS_INPUT_REGISTER 801 1 u16 0 0 0
Superheat reference EVI (EB107) MODBUS_INPUT_REGISTER 802 10 °C s16 0 0 0
Superheat EVI (EB107) MODBUS_INPUT_REGISTER 803 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB107) MODBUS_INPUT_REGISTER 804 10 °C s16 0 0 0
Superheat temp. reference EVI (EB107) MODBUS_INPUT_REGISTER 805 10 °C s16 0 0 0
Set point value EVI (EB107) MODBUS_INPUT_REGISTER 806 10 °C s16 0 0 0
EVI PV (EB107) MODBUS_INPUT_REGISTER 807 10 °C s16 0 0 0
EEV-te-error average open (EVI)(EB107) MODBUS_INPUT_REGISTER 808 10 °C s16 0 0 0
Degree of opening EVI (EB107) MODBUS_INPUT_REGISTER 809 1 u16 0 0 0
Max fan speed (EB106) MODBUS_INPUT_REGISTER 812 1 rpm u16 0 0 0
Generated power heating (EB106) MODBUS_INPUT_REGISTER 816 10 kW u16 0 0 0
Defrosting index (EB106) MODBUS_INPUT_REGISTER 818 1 u16 0 0 0
Superheat reference EEV (EB106) MODBUS_INPUT_REGISTER 819 10 °C s16 0 0 0
Superheat EEV (EB106) MODBUS_INPUT_REGISTER 820 10 °C s16 0 0 0
EEV-ssh-error (EB106) MODBUS_INPUT_REGISTER 821 10 °C s16 0 0 0
Superheat temp. reference EEV (EB106) MODBUS_INPUT_REGISTER 822 10 °C s16 0 0 0
Set point value EEV (EB106) MODBUS_INPUT_REGISTER 823 10 °C s16 0 0 0
EEV PV (EB106) MODBUS_INPUT_REGISTER 824 10 °C s16 0 0 0
EEV-te-error average open (EB106) MODBUS_INPUT_REGISTER 825 10 °C s16 0 0 0
Degree of opening EEV (EB106) MODBUS_INPUT_REGISTER 826 1 u16 0 0 0
Superheat reference EVI (EB106) MODBUS_INPUT_REGISTER 827 10 °C s16 0 0 0
Superheat EVI (EB106) MODBUS_INPUT_REGISTER 828 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB106) MODBUS_INPUT_REGISTER 829 10 °C s16 0 0 0
Superheat temp. reference EVI (EB106) MODBUS_INPUT_REGISTER 830 10 °C s16 0 0 0
Set point value EVI (EB106) MODBUS_INPUT_REGISTER 831 10 °C s16 0 0 0
EVI PV (EB106) MODBUS_INPUT_REGISTER 832 10 °C s16 0 0 0
EEV-te-error average open (EVI)(EB106) MODBUS_INPUT_REGISTER 833 10 °C s16 0 0 0
Degree of opening EVI (EB106) MODBUS_INPUT_REGISTER 834 1 u16 0 0 0
Max fan speed (EB105) MODBUS_INPUT_REGISTER 837 1 rpm u16 0 0 0
Min fan speed (EB105) MODBUS_INPUT_REGISTER 838 1 rpm u16 0 0 0
Generated power heating (EB105) MODBUS_INPUT_REGISTER 841 10 kW u16 0 0 0
Defrosting index (EB105) MODBUS_INPUT_REGISTER 843 1 u16 0 0 0
Superheat reference EEV (EB105) MODBUS_INPUT_REGISTER 844 10 °C s16 0 0 0
Superheat EEV (EB105) MODBUS_INPUT_REGISTER 845 10 °C s16 0 0 0
EEV-ssh-error (EB105) MODBUS_INPUT_REGISTER 846 10 °C s16 0 0 0
Superheat temp. reference EEV (EB105) MODBUS_INPUT_REGISTER 847 10 °C s16 0 0 0
Set point value EEV (EB105) MODBUS_INPUT_REGISTER 848 10 °C s16 0 0 0
EEV PV (EB105) MODBUS_INPUT_REGISTER 849 10 °C s16 0 0 0
EEV-te-error average open (EB105) MODBUS_INPUT_REGISTER 850 10 °C s16 0 0 0
Degree of opening EEV (EB105) MODBUS_INPUT_REGISTER 851 1 u16 0 0 0
Superheat reference EVI (EB105) MODBUS_INPUT_REGISTER 852 10 °C s16 0 0 0
Superheat EVI (EB105) MODBUS_INPUT_REGISTER 853 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB105) MODBUS_INPUT_REGISTER 854 10 °C s16 0 0 0
Superheat temp. reference EVI (EB105) MODBUS_INPUT_REGISTER 855 10 °C s16 0 0 0
Set point value EVI (EB105) MODBUS_INPUT_REGISTER 856 10 °C s16 0 0 0
EVI PV (EB105) MODBUS_INPUT_REGISTER 857 10 °C s16 0 0 0
EEV-te-error average open (EVI)(EB105) MODBUS_INPUT_REGISTER 858 10 °C s16 0 0 0
Degree of opening EVI (EB105) MODBUS_INPUT_REGISTER 859 1 u16 0 0 0
Max fan speed (EB104) MODBUS_INPUT_REGISTER 862 1 rpm u16 0 0 0
Min fan speed (EB104) MODBUS_INPUT_REGISTER 863 1 rpm u16 0 0 0
Generated power heating (EB104) MODBUS_INPUT_REGISTER 866 10 kW u16 0 0 0
Defrosting index (EB104) MODBUS_INPUT_REGISTER 868 1 u16 0 0 0
Superheat reference EEV (EB104) MODBUS_INPUT_REGISTER 869 10 °C s16 0 0 0
Superheat EEV (EB104) MODBUS_INPUT_REGISTER 870 10 °C s16 0 0 0
EEV-ssh-error (EB104) MODBUS_INPUT_REGISTER 871 10 °C s16 0 0 0
Superheat temp. reference EEV (EB104) MODBUS_INPUT_REGISTER 872 10 °C s16 0 0 0
Set point value EEV (EB104) MODBUS_INPUT_REGISTER 873 10 °C s16 0 0 0
EEV PV (EB104) MODBUS_INPUT_REGISTER 874 10 °C s16 0 0 0
EEV-te-error average open (EB104) MODBUS_INPUT_REGISTER 875 10 °C s16 0 0 0
Degree of opening EEV (EB104) MODBUS_INPUT_REGISTER 876 1 u16 0 0 0
Superheat reference EVI (EB104) MODBUS_INPUT_REGISTER 877 10 °C s16 0 0 0
Superheat EVI (EB104) MODBUS_INPUT_REGISTER 878 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB104) MODBUS_INPUT_REGISTER 879 10 °C s16 0 0 0
Superheat temp. reference EVI (EB104) MODBUS_INPUT_REGISTER 880 10 °C s16 0 0 0
Set point value EVI (EB104) MODBUS_INPUT_REGISTER 881 10 °C s16 0 0 0
EVI PV (EB104) MODBUS_INPUT_REGISTER 882 10 °C s16 0 0 0
EEV-te-error average open (EVI)(EB104) MODBUS_INPUT_REGISTER 883 10 °C s16 0 0 0
Degree of opening EVI (EB104) MODBUS_INPUT_REGISTER 884 1 u16 0 0 0
Max fan speed (EB103) MODBUS_INPUT_REGISTER 887 1 rpm u16 0 0 0
Min fan speed (EB103) MODBUS_INPUT_REGISTER 888 1 rpm u16 0 0 0
Generated power heating (EB103) MODBUS_INPUT_REGISTER 891 10 kW u16 0 0 0
Defrosting index (EB103) MODBUS_INPUT_REGISTER 893 1 u16 0 0 0
Superheat reference EEV (EB103) MODBUS_INPUT_REGISTER 894 10 °C s16 0 0 0
Superheat EEV (EB103) MODBUS_INPUT_REGISTER 895 10 °C s16 0 0 0
EEV-ssh-error (EB103) MODBUS_INPUT_REGISTER 896 10 °C s16 0 0 0
Superheat temp. reference EEV (EB103) MODBUS_INPUT_REGISTER 897 10 °C s16 0 0 0
Set point value EEV (EB103) MODBUS_INPUT_REGISTER 898 10 °C s16 0 0 0
EEV PV (EB103) MODBUS_INPUT_REGISTER 899 10 °C s16 0 0 0
EEV-te-error average open (EB103) MODBUS_INPUT_REGISTER 900 10 °C s16 0 0 0
Degree of opening EEV (EB103) MODBUS_INPUT_REGISTER 901 1 u16 0 0 0
Superheat reference EVI (EB103) MODBUS_INPUT_REGISTER 902 10 °C s16 0 0 0
Superheat EVI (EB103) MODBUS_INPUT_REGISTER 903 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB103) MODBUS_INPUT_REGISTER 904 10 °C s16 0 0 0
Superheat temp. reference EVI (EB103) MODBUS_INPUT_REGISTER 905 10 °C s16 0 0 0
Set point value EVI (EB103) MODBUS_INPUT_REGISTER 906 10 °C s16 0 0 0
EVI PV (EB103) MODBUS_INPUT_REGISTER 907 10 °C s16 0 0 0
EEV-te-error average open (EVI)(EB103) MODBUS_INPUT_REGISTER 908 10 °C s16 0 0 0
Degree of opening EVI (EB103) MODBUS_INPUT_REGISTER 909 1 u16 0 0 0
Fan speed (EB102) MODBUS_INPUT_REGISTER 911 1 rpm u16 0 0 0
Max fan speed (EB102) MODBUS_INPUT_REGISTER 912 1 rpm u16 0 0 0
Min fan speed (EB102) MODBUS_INPUT_REGISTER 913 1 rpm u16 0 0 0
Generated power heating (EB102 MODBUS_INPUT_REGISTER 916 10 kW u16 0 0 0
Defrosting index (EB102) MODBUS_INPUT_REGISTER 918 1 u16 0 0 0
Superheat reference EEV (EB102) MODBUS_INPUT_REGISTER 919 10 °C s16 0 0 0
Superheat EEV (EB102) MODBUS_INPUT_REGISTER 920 10 °C s16 0 0 0
EEV-ssh-error (EB102) MODBUS_INPUT_REGISTER 921 10 °C s16 0 0 0
Superheat temp. reference EEV (EB101) MODBUS_INPUT_REGISTER 922 10 °C s16 0 0 0
Set point value EEV (EB102) MODBUS_INPUT_REGISTER 923 10 °C s16 0 0 0
EEV PV (EB102) MODBUS_INPUT_REGISTER 924 10 °C s16 0 0 0
EEV-te-error average open (EB102) MODBUS_INPUT_REGISTER 925 10 °C s16 0 0 0
Degree of opening EEV (EB102) MODBUS_INPUT_REGISTER 926 1 u16 0 0 0
Superheat reference EVI (EB102) MODBUS_INPUT_REGISTER 927 10 °C s16 0 0 0
Superheat EVI (EB102) MODBUS_INPUT_REGISTER 928 10 °C s16 0 0 0
EEV-ssh-error (EVI)(EB102) MODBUS_INPUT_REGISTER 929 10 °C s16 0 0 0
Superheat temp. reference EVI (EB102) MODBUS_INPUT_REGISTER 930 10 °C s16 0 0 0
Set point value EVI (EB102) MODBUS_INPUT_REGISTER 931 10 °C s16 0 0 0
EVI PV (EB102) MODBUS_INPUT_REGISTER 932 10 °C s16 0 0 0
EEV-te-error average open (EVI)(EB102) MODBUS_INPUT_REGISTER 933 10 °C s16 0 0 0
Degree of opening EVI (EB102) MODBUS_INPUT_REGISTER 934 1 u16 0 0 0
Wind speed, weather forecast MODBUS_INPUT_REGISTER 960 10 u16 0 0 0
Humidity, weather forecast MODBUS_INPUT_REGISTER 961 10 % u16 0 0 0
Temperature, weather forecast MODBUS_INPUT_REGISTER 962 10 °C s16 0 0 0
Temperature, weather data (forecast) MODBUS_INPUT_REGISTER 963 10 °C s16 0 0 0
Limit DM MODBUS_HOLDING_REGISTER 18 10 DM s16 -30000 30000 0
Calculated supply climate system 3 MODBUS_INPUT_REGISTER 1015 10 °C s16 0 0 0
Calculated supply climate system 2 MODBUS_INPUT_REGISTER 1016 10 °C s16 0 0 0
Calculated supply climate system 1 MODBUS_INPUT_REGISTER 1017 10 °C s16 0 0 0
Class 1 alarm MODBUS_INPUT_REGISTER 2195 1 u8 0 0 0
Frost protection status MODBUS_INPUT_REGISTER 1018 1 u16 0 0 0
Cooling status MODBUS_INPUT_REGISTER 1019 1 u8 0 0 0
Total run time additional heat MODBUS_INPUT_REGISTER 1025 10 h s32 0 1000000 0
Power internal additional heat MODBUS_INPUT_REGISTER 1027 100 kW s16 0 0 0
Priority MODBUS_INPUT_REGISTER 1028 1 u8 0 0 0
Operating mode internal add. heat MODBUS_INPUT_REGISTER 1029 1 u8 0 0 0
Oper. mode shunt climate system 4 MODBUS_INPUT_REGISTER 1030 1 u8 0 0 0
Oper. mode shunt climate system 3 MODBUS_INPUT_REGISTER 1031 1 u8 0 0 0
Oper. mode shunt climate system 2 MODBUS_INPUT_REGISTER 1032 1 u8 0 0 0
Oper. mode shunt climate system 1 MODBUS_INPUT_REGISTER 1033 1 u8 0 0 0
Operating. mode shunt controlled additional heat MODBUS_INPUT_REGISTER 1034 1 u8 0 0 0
Fan mode 1 MODBUS_INPUT_REGISTER 1037 1 % u8 0 0 0
Current hot water mode MODBUS_INPUT_REGISTER 1038 1 s8 0 0 0
Min frequency compressor MODBUS_INPUT_REGISTER 1041 1 Hz s16 0 0 0
Max frequency compressor MODBUS_INPUT_REGISTER 1042 1 Hz s16 0 0 0
Compressor frequency, current MODBUS_INPUT_REGISTER 1046 10 Hz u16 0 0 0
Inverter temperature MODBUS_INPUT_REGISTER 1047 10 °C s16 0 0 0
Compressor power input MODBUS_INPUT_REGISTER 1048 1 W u16 0 0 0
Current compressor MODBUS_INPUT_REGISTER 1052 1 mA s16 0 0 0
Blocking cooling MODBUS_INPUT_REGISTER 1053 1 u8 0 0 0
External adjustment climate system 4 MODBUS_INPUT_REGISTER 1054 1 u8 0 0 0
External adjustment climate system 3 MODBUS_INPUT_REGISTER 1055 1 u8 0 0 0
External adjustment climate system 2 MODBUS_INPUT_REGISTER 1056 1 u8 0 0 0
External adjustment climate system 1 MODBUS_INPUT_REGISTER 1057 1 u8 0 0 0
External blocking MODBUS_INPUT_REGISTER 1058 1 u8 0 0 0
Blocked MODBUS_INPUT_REGISTER 1059 1 u8 0 0 0
External blocking, active cooling (HPAC) MODBUS_INPUT_REGISTER 1060 1 u8 0 0 0
External blocking, passive cooling (HPAC) MODBUS_INPUT_REGISTER 1061 1 u8 0 0 0
Step controlled add. heat blocking MODBUS_INPUT_REGISTER 1062 1 u8 0 0 0
Hot water circulation (GP11) MODBUS_INPUT_REGISTER 1063 1 u8 0 0 0
Compressor frequency MODBUS_INPUT_REGISTER 1065 1 Hz u16 0 0 0
Op.time electrical heater for hot water MODBUS_INPUT_REGISTER 1069 10 h s32 0 9999999 0
Compressor power input, average MODBUS_INPUT_REGISTER 1075 1 W s16 0 0 0
More hot water status MODBUS_INPUT_REGISTER 1078 1 u8 0 0 0
Relay status (HPAC) MODBUS_INPUT_REGISTER 1079 1 u8 0 0 0
Holiday function status MODBUS_HOLDING_REGISTER 19 1 s8 0 0 0
Compressor starter MODBUS_INPUT_REGISTER 1083 1 s32 -2147483648 2147483647 0
Total run time compressor MODBUS_INPUT_REGISTER 1087 1 h s32 -2147483648 2147483647 0
Total run time compressor hot water MODBUS_INPUT_REGISTER 1091 1 h s32 -2147483648 2147483647 0
Operating mode compressor MODBUS_INPUT_REGISTER 1094 1 u8 0 0 0
Operating mode heating medium pump MODBUS_INPUT_REGISTER 1096 1 u8 0 0 0
Operating mode brine pump MODBUS_INPUT_REGISTER 1098 1 u8 0 0 0
Compressor status MODBUS_INPUT_REGISTER 1100 1 u8 0 0 0
Heating medium pump speed (GP1) MODBUS_INPUT_REGISTER 1102 1 % u8 0 0 0
Brine pump speed (GP2) MODBUS_INPUT_REGISTER 1104 1 % u8 0 0 0
Docked compressors heating MODBUS_INPUT_REGISTER 1108 1 u8 0 0 0
Docked compressors hot water MODBUS_INPUT_REGISTER 1109 1 u8 0 0 0
Docked compressors pool 1 MODBUS_INPUT_REGISTER 1110 1 u8 0 0 0
Diverter valve hot water (QN10) MODBUS_INPUT_REGISTER 2196 1 u8 0 0 0
Cooling activated (FLM 4) MODBUS_INPUT_REGISTER 1111 1 u8 0 0 0
Cooling activated (FLM 3) MODBUS_INPUT_REGISTER 1112 1 u8 0 0 0
Cooling activated (FLM 2) MODBUS_INPUT_REGISTER 1113 1 u8 0 0 0
Cooling activated (FLM 1) MODBUS_INPUT_REGISTER 1114 1 u8 0 0 0
Relay status, base board (EB100-EP14) MODBUS_INPUT_REGISTER 1117 1 u8 0 0 0
Relay status, imm. heat. board (EB100-EP14) MODBUS_INPUT_REGISTER 1119 1 u16 0 0 0
Current status MODBUS_INPUT_REGISTER 1120 1 u32 0 0 0
Functionality, heat pump (EP14) MODBUS_INPUT_REGISTER 1122 1 u32 0 0 0
Active heat pumps MODBUS_INPUT_REGISTER 1124 1 u16 0 0 0
Functionality, heat pump (EP15) MODBUS_INPUT_REGISTER 1125 1 u32 0 0 0
Operating mode HW comfort MODBUS_INPUT_REGISTER 1129 1 u8 0 0 0
Operating mode HW comfort additional heat MODBUS_INPUT_REGISTER 1130 1 u8 0 0 0
Blocked MODBUS_INPUT_REGISTER 1131 1 u8 0 0 0
Blocked MODBUS_INPUT_REGISTER 1132 1 u8 0 0 0
Pool 2 (QN19) MODBUS_INPUT_REGISTER 1133 1 u8 0 0 0
Pool 1 (QN19) MODBUS_INPUT_REGISTER 1134 1 u8 0 0 0
Docked compressors pool 2 MODBUS_INPUT_REGISTER 1135 1 u8 0 0 0
Version (EB100) MODBUS_INPUT_REGISTER 1496 1 u16 0 0 0
Heat pump type (EB100) MODBUS_INPUT_REGISTER 1497 1 u8 0 0 0
Compressor size (EB100) MODBUS_INPUT_REGISTER 1498 1 u8 0 0 0
Compressor, oper. time, total (EB100-EP15) MODBUS_INPUT_REGISTER 1515 1 h u32 0 0 0
Compressor, oper. time, hot water (EB100-EP15) MODBUS_INPUT_REGISTER 1517 1 h u32 0 0 0
Return line (EB100-BT3) MODBUS_INPUT_REGISTER 1520 10 °C s16 0 0 0
Brine in (EB100-BT10) MODBUS_INPUT_REGISTER 1521 10 °C s16 0 0 0
Brine out (EB100-BT11) MODBUS_INPUT_REGISTER 1522 10 °C s16 0 0 0
Condenser (EB100-BT2) MODBUS_INPUT_REGISTER 1523 10 °C s16 0 0 0
Discharge (EB100-BT14) MODBUS_INPUT_REGISTER 1524 10 °C s16 0 0 0
Liquid line (EB100-BT15) MODBUS_INPUT_REGISTER 1525 10 °C s16 0 0 0
Suction gas (EB100-BT17) MODBUS_INPUT_REGISTER 1526 10 °C s16 0 0 0
Compressor sensor (EB100-BT29) MODBUS_INPUT_REGISTER 1527 10 °C s16 0 0 0
Low press (EB100-BP8) MODBUS_INPUT_REGISTER 1528 10 °C s16 0 0 0
Compressor status (EB100) MODBUS_INPUT_REGISTER 1529 1 u8 0 0 0
Compressor, time to start (EB100-EP14) MODBUS_INPUT_REGISTER 1530 1 min u8 0 0 0
Relay status (EB100-EP14) MODBUS_INPUT_REGISTER 1531 1 u16 0 0 0
Heating medium pump (EB100) MODBUS_INPUT_REGISTER 1532 1 % u8 0 0 0
Brine pump (EB100) MODBUS_INPUT_REGISTER 1533 1 % u8 0 0 0
Compressor, number of starts (EB100-EP14) MODBUS_INPUT_REGISTER 1534 1 u32 0 0 0
Compressor, oper. time, total (EB100-EP14) MODBUS_INPUT_REGISTER 1536 1 h u32 0 0 0
Compressor, oper. time, hot water (EB100-EP14) MODBUS_INPUT_REGISTER 1538 1 h u32 0 0 0
Compressor, requested (EB108-EP15) MODBUS_INPUT_REGISTER 1541 1 u8 0 0 0
Compressor, requested (EB108-EP14) MODBUS_INPUT_REGISTER 1542 1 u8 0 0 0
Compressor, requested (EB107-EP15) MODBUS_INPUT_REGISTER 1543 1 u8 0 0 0
Compressor, requested (EB107-EP14) MODBUS_INPUT_REGISTER 1544 1 u8 0 0 0
Compressor, requested (EB106-EP15) MODBUS_INPUT_REGISTER 1545 1 u8 0 0 0
Compressor, requested (EB106-EP14) MODBUS_INPUT_REGISTER 1546 1 u8 0 0 0
Compressor, requested (EB105-EP15) MODBUS_INPUT_REGISTER 1547 1 u8 0 0 0
Compressor, requested (EB105-EP14) MODBUS_INPUT_REGISTER 1548 1 u8 0 0 0
Compressor, requested (EB104-EP15) MODBUS_INPUT_REGISTER 1549 1 u8 0 0 0
Compressor, requested (EB104-EP14) MODBUS_INPUT_REGISTER 1550 1 u8 0 0 0
Compressor, requested (EB103-EP15) MODBUS_INPUT_REGISTER 1551 1 u8 0 0 0
Compressor, requested (EB103-EP14) MODBUS_INPUT_REGISTER 1552 1 u8 0 0 0
Compressor, requested (EB102-EP15) MODBUS_INPUT_REGISTER 1553 1 u8 0 0 0
Compressor, requested (EB102-EP14) MODBUS_INPUT_REGISTER 1554 1 u8 0 0 0
Compressor, requested (EB101-EP15) MODBUS_INPUT_REGISTER 1555 1 u8 0 0 0
Compressor, requested (EB101-EP14) MODBUS_INPUT_REGISTER 1556 1 u8 0 0 0
Date, periodic hot water MODBUS_INPUT_REGISTER 1561 1 - - - -
Blocked compressors MODBUS_INPUT_REGISTER 2174 1 u32 0 0 0
Cooling degree minutes MODBUS_HOLDING_REGISTER 20 10 DM s16 -30000 30000 0
Calculated cooling supply climate system 3 MODBUS_INPUT_REGISTER 1565 10 °C s16 0 0 0
Calculated cooling supply climate system 2 MODBUS_INPUT_REGISTER 1566 10 °C s16 0 0 0
Calculated cooling supply climate system 1 MODBUS_INPUT_REGISTER 1567 10 °C s16 0 0 0
Status (ACS) MODBUS_INPUT_REGISTER 1568 1 u8 0 0 0
Status, heating dumping (ACS) MODBUS_INPUT_REGISTER 1569 1 u8 0 0 0
Status, cooling dumping (ACS) MODBUS_INPUT_REGISTER 1570 1 u8 0 0 0
Used compressors hot water MODBUS_INPUT_REGISTER 1571 1 u8 0 0 0
Used compressors heating MODBUS_INPUT_REGISTER 1572 1 u8 0 0 0
Used compressors pool 1 MODBUS_INPUT_REGISTER 1573 1 u8 0 0 0
Used compressors pool 2 MODBUS_INPUT_REGISTER 1574 1 u8 0 0 0
Used compressors cooling MODBUS_INPUT_REGISTER 1588 1 u8 0 0 0
(EB100-EP15-BT28) MODBUS_INPUT_REGISTER 1623 10 °C s16 0 0 0
(EB100-EP15-BT16) MODBUS_INPUT_REGISTER 1624 10 °C s16 0 0 0
(EB100-EP14-BT28) MODBUS_INPUT_REGISTER 1625 10 °C s16 0 0 0
(EB100-EP14-BT16) MODBUS_INPUT_REGISTER 1626 10 °C s16 0 0 0
Docked compressors external control MODBUS_INPUT_REGISTER 1628 1 u8 0 0 0
Bit register (EB100) MODBUS_INPUT_REGISTER 1687 1 u8 0 0 0
Controlling hot water sensor (EB100-BT6) MODBUS_INPUT_REGISTER 1688 10 °C s16 0 0 0
Display hot water sensor (EB100-BT7) MODBUS_INPUT_REGISTER 1689 10 °C s16 0 0 0
Supply temperature sensor (EB100-BT2) MODBUS_INPUT_REGISTER 1690 10 °C s16 0 0 0
Compressor status (EB100-EP15) MODBUS_INPUT_REGISTER 1691 1 u8 0 0 0
Compressor status (EB100-EP14) MODBUS_INPUT_REGISTER 1692 1 u8 0 0 0
Docked compressors cooling MODBUS_INPUT_REGISTER 1694 1 u8 0 0 0
BP4, unprocessed (EB108-EP15) MODBUS_INPUT_REGISTER 1695 1 s16 0 0 0
Low pressure (EB108-EP15--BP8) MODBUS_INPUT_REGISTER 1697 10 bar s16 0 0 0
Prot. status (EB108-EP15) MODBUS_INPUT_REGISTER 1699 1 u16 0 0 0
Defrosting (EB108-EP15) MODBUS_INPUT_REGISTER 1700 1 u8 0 0 0
BP4, unprocessed (EB108-EP14) MODBUS_INPUT_REGISTER 1702 1 s16 0 0 0
Defrosting (EB108) MODBUS_INPUT_REGISTER 1707 1 u8 0 0 0
BP4, unprocessed (EB107-EP15) MODBUS_INPUT_REGISTER 1709 1 s16 0 0 0
Low pressure (EB107-EP15--BP8) MODBUS_INPUT_REGISTER 1711 10 bar s16 0 0 0
Prot. status (EB107-EP15) MODBUS_INPUT_REGISTER 1713 1 u16 0 0 0
Defrosting (EB107-EP15) MODBUS_INPUT_REGISTER 1714 1 u8 0 0 0
Power (EB107-EP15) MODBUS_INPUT_REGISTER 1715 1 kW u8 0 0 0
BP4, unprocessed (EB107-EP14) MODBUS_INPUT_REGISTER 1716 1 s16 0 0 0
Defrosting (EB107) MODBUS_INPUT_REGISTER 1721 1 u8 0 0 0
Power (EB107-EP14) MODBUS_INPUT_REGISTER 1722 1 kW u8 0 0 0
BP4, unprocessed (EB106-EP15) MODBUS_INPUT_REGISTER 1723 1 s16 0 0 0
Low pressure (EB106-EP15--BP8) MODBUS_INPUT_REGISTER 1725 10 bar s16 0 0 0
Prot. status (EB106-EP15) MODBUS_INPUT_REGISTER 1727 1 u16 0 0 0
Defrosting (EB106-EP15) MODBUS_INPUT_REGISTER 1728 1 u8 0 0 0
Power (EB106-EP15) MODBUS_INPUT_REGISTER 1729 1 kW u8 0 0 0
BP4, unprocessed (EB106-EP14) MODBUS_INPUT_REGISTER 1730 1 s16 0 0 0
Defrosting (EB106) MODBUS_INPUT_REGISTER 1735 1 u8 0 0 0
Power (EB106-EP14) MODBUS_INPUT_REGISTER 1736 1 kW u8 0 0 0
BP4, unprocessed (EB105-EP15) MODBUS_INPUT_REGISTER 1737 1 s16 0 0 0
Low pressure (EB105-EP15--BP8) MODBUS_INPUT_REGISTER 1739 10 bar s16 0 0 0
Prot. status (EB105-EP15) MODBUS_INPUT_REGISTER 1741 1 u16 0 0 0
Defrosting (EB105-EP15) MODBUS_INPUT_REGISTER 1742 1 u8 0 0 0
Power (EB105-EP15) MODBUS_INPUT_REGISTER 1743 1 kW u8 0 0 0
BP4, unprocessed (EB105-EP14) MODBUS_INPUT_REGISTER 1744 1 s16 0 0 0
Defrosting (EB105) MODBUS_INPUT_REGISTER 1749 1 u8 0 0 0
Power (EB105-EP15) MODBUS_INPUT_REGISTER 1750 1 kW u8 0 0 0
BP4, unprocessed (EB104-EP15) MODBUS_INPUT_REGISTER 1751 1 s16 0 0 0
Low pressure (EB104-EP15--BP8) MODBUS_INPUT_REGISTER 1753 10 bar s16 0 0 0
Prot. status (EB104-EP15) MODBUS_INPUT_REGISTER 1755 1 u16 0 0 0
Low pressure (EB103-EP15--BP8) MODBUS_INPUT_REGISTER 1767 10 bar s16 0 0 0
BP4, unprocessed (EB103-EP14) MODBUS_INPUT_REGISTER 1772 1 s16 0 0 0
Defrosting (EB103) MODBUS_INPUT_REGISTER 1777 1 u8 0 0 0
Power (EB103-EP14) MODBUS_INPUT_REGISTER 1778 1 kW u8 0 0 0
BP4, unprocessed (EB102-EP15) MODBUS_INPUT_REGISTER 1779 1 s16 0 0 0
Low pressure (EB102-EP15--BP8) MODBUS_INPUT_REGISTER 1781 10 bar s16 0 0 0
Prot. status (EB102-EP15) MODBUS_INPUT_REGISTER 1783 1 u16 0 0 0
Defrosting (EB102-EP15) MODBUS_INPUT_REGISTER 1784 1 u8 0 0 0
Power (EB102-EP15) MODBUS_INPUT_REGISTER 1785 1 kW u8 0 0 0
BP4, unprocessed (EB102-EP14) MODBUS_INPUT_REGISTER 1786 1 s16 0 0 0
Defrosting (EB102) MODBUS_INPUT_REGISTER 1791 1 u8 0 0 0
Power (EB102-EP14) MODBUS_INPUT_REGISTER 1792 1 kW u8 0 0 0
BP4, unprocessed (EB101-EP15) MODBUS_INPUT_REGISTER 1793 1 s16 0 0 0
Low pressure (EB101-EP15-BP8) MODBUS_INPUT_REGISTER 1795 10 bar s16 0 0 0
Prot. status (EB101-EP15) MODBUS_INPUT_REGISTER 1797 1 u16 0 0 0
Defrosting (EB101-EP15) MODBUS_INPUT_REGISTER 1798 1 u8 0 0 0
Power (EB101-EP15) MODBUS_INPUT_REGISTER 1799 1 kW u8 0 0 0
BP4, unprocessed (EB101-EP14) MODBUS_INPUT_REGISTER 1800 1 s16 0 0 0
Defrosting (EB101) MODBUS_INPUT_REGISTER 1805 1 u8 0 0 0
Power (EB101-EP14) MODBUS_INPUT_REGISTER 1806 1 kW u8 0 0 0
BP4, unprocessed (EB100-EP15) MODBUS_INPUT_REGISTER 1807 1 s16 0 0 0
Pressure sensor, condenser (EB100-EP15-BP4) MODBUS_INPUT_REGISTER 1808 10 bar s16 0 0 0
Low pressure (EB100-EP15-BP8) MODBUS_INPUT_REGISTER 1809 10 bar s16 0 0 0
Prot. status (EB100-EP15) MODBUS_INPUT_REGISTER 1811 1 u16 0 0 0
Defrosting (EB100-EP15) MODBUS_INPUT_REGISTER 1812 1 u8 0 0 0
Power (EB100-EP15) MODBUS_INPUT_REGISTER 1813 1 kW u8 0 0 0
BP4, unprocessed (EB100-EP14) MODBUS_INPUT_REGISTER 1814 1 s16 0 0 0
Pressure sensor, condenser (EB100-EP14-BP4) MODBUS_INPUT_REGISTER 1815 10 bar s16 0 0 0
Low pressure (EB100-EP14-BP8) MODBUS_INPUT_REGISTER 1816 10 bar s16 0 0 0
Prot. status (EB100-EP14) MODBUS_INPUT_REGISTER 1818 1 u16 0 0 0
Defrosting (EB100-EP14) MODBUS_INPUT_REGISTER 1819 1 u8 0 0 0
Power (EB100-EP14) MODBUS_INPUT_REGISTER 1820 1 kW u8 0 0 0
Climate system 4 MODBUS_INPUT_REGISTER 1823 1 u8 0 0 0
Climate system 3 MODBUS_INPUT_REGISTER 1824 1 u8 0 0 0
Climate system 2 MODBUS_INPUT_REGISTER 1825 1 u8 0 0 0
Climate system 1 (HMP) MODBUS_INPUT_REGISTER 1826 1 u8 0 0 0
Pool 2 pump status MODBUS_INPUT_REGISTER 1827 1 u8 0 0 0
Pool 1 pump status MODBUS_INPUT_REGISTER 1828 1 u8 0 0 0
ACS EQ1-QN12 MODBUS_INPUT_REGISTER 1830 1 u8 0 0 0
ACS EQ1-GP20 MODBUS_INPUT_REGISTER 1831 1 u8 0 0 0
Passive cooling shunt MODBUS_INPUT_REGISTER 1832 1 u8 0 0 0
Passive cooling pump (GP13) MODBUS_INPUT_REGISTER 1833 1 u8 0 0 0
Oper. mode groundwater pump MODBUS_INPUT_REGISTER 1835 1 u8 0 0 0
Alarm number (EB100-EP15) MODBUS_INPUT_REGISTER 1837 1 u16 0 0 0
Alarm number (EB100-EP14) MODBUS_INPUT_REGISTER 1838 1 u16 0 0 0
Requested compressor frequency (EB108-EP15) MODBUS_INPUT_REGISTER 1839 1 Hz u8 0 0 0
Requested compressor frequency (EB107-EP15) MODBUS_INPUT_REGISTER 1841 1 Hz u8 0 0 0
Requested compressor frequency (EB106-EP15) MODBUS_INPUT_REGISTER 1843 1 Hz u8 0 0 0
Requested compressor frequency (EB105-EP15) MODBUS_INPUT_REGISTER 1845 1 Hz u8 0 0 0
Requested compressor frequency (EB104-EP15) MODBUS_INPUT_REGISTER 1847 1 Hz u8 0 0 0
Requested compressor frequency (EB103-EP15) MODBUS_INPUT_REGISTER 1849 1 Hz u8 0 0 0
Requested compressor frequency (EB102-EP15) MODBUS_INPUT_REGISTER 1851 1 Hz u8 0 0 0
Requested compressor frequency (EB101-EP15) MODBUS_INPUT_REGISTER 1853 1 Hz u8 0 0 0
Requested compressor frequency (EP15) MODBUS_INPUT_REGISTER 1855 1 Hz u8 0 0 0
Requested compressor frequency MODBUS_INPUT_REGISTER 1856 1 Hz u8 0 0 0
Operating mode, shunt controlled brine (QN41) MODBUS_INPUT_REGISTER 2410 1 u8 0 0 0
Low press. sensor, unprocessed (EB100-EP15) MODBUS_INPUT_REGISTER 1905 1 s16 0 0 0
Current sensor (EB100-EP15) MODBUS_INPUT_REGISTER 1906 10 A s16 0 0 0
Low press. sensor, unprocessed (EB100-EP14) MODBUS_INPUT_REGISTER 1908 1 s16 0 0 0
Current sensor (EB100-EP14) MODBUS_INPUT_REGISTER 1909 10 A s16 0 0 0
SG ready, input A MODBUS_INPUT_REGISTER 1912 1 u8 0 0 0
SG ready, input B MODBUS_INPUT_REGISTER 1913 1 u8 0 0 0
Hot water comfort mode (SPA) MODBUS_INPUT_REGISTER 1915 1 s8 0 0 0
Pool offset (SPA) MODBUS_INPUT_REGISTER 1916 1 s8 0 0 0
Cooling offset (SPA) MODBUS_INPUT_REGISTER 1917 1 s8 0 0 0
Operating mode (Smart Price Adaption) MODBUS_INPUT_REGISTER 1918 1 u8 0 0 0
Brine pump dT current MODBUS_INPUT_REGISTER 1919 10 s16 0 0 0
Brine pump dT set point value MODBUS_INPUT_REGISTER 1920 10 s16 0 0 0
Evaporator 2 (EB100-EP15-BT16) MODBUS_INPUT_REGISTER 1969 10 °C s16 0 0 0
Temperature, inverter (EB100-EP15) MODBUS_INPUT_REGISTER 1970 10 °C s16 0 0 0
fan speed (EB100-EP15) MODBUS_INPUT_REGISTER 1971 1 u8 0 0 0
Evaporator 2 (EB100-EP14-BT16) MODBUS_INPUT_REGISTER 1972 10 °C s16 0 0 0
Temperature, inverter (EB100-EP14) MODBUS_INPUT_REGISTER 1973 10 °C s16 0 0 0
fan speed (EB100-EP14) MODBUS_INPUT_REGISTER 1974 1 u8 0 0 0
Alarm number MODBUS_INPUT_REGISTER 1975 1 s16 0 0 0
Reset alarm MODBUS_HOLDING_REGISTER 22 1 u8 0 0 0
Non module-specific alarm numbers MODBUS_INPUT_REGISTER 1976 1 s16 0 0 0
Heating curve climate system 3 MODBUS_HOLDING_REGISTER 24 1 s8 0 15 9
Heating curve climate system 2 MODBUS_HOLDING_REGISTER 25 1 s8 0 15 9
Heating curve climate system 1 MODBUS_HOLDING_REGISTER 26 1 s8 0 15 9
Heating offset climate system 1 MODBUS_HOLDING_REGISTER 30 1 s8 -10 10 0
Min supply climate system 3 MODBUS_HOLDING_REGISTER 32 10 °C s16 50 800 200
Min supply climate system 2 MODBUS_HOLDING_REGISTER 33 10 °C s16 50 800 200
Min supply climate system 1 MODBUS_HOLDING_REGISTER 34 10 °C s16 50 800 200
Max supply climate system 3 MODBUS_HOLDING_REGISTER 36 10 °C s16 50 800 600
Max supply climate system 2 MODBUS_HOLDING_REGISTER 37 10 °C s16 50 800 600
Max supply climate system 1 MODBUS_HOLDING_REGISTER 38 10 °C s16 50 800 600
Own curve, heating P7 MODBUS_HOLDING_REGISTER 39 1 °C s8 5 80 15
Own curve, heating P6 MODBUS_HOLDING_REGISTER 40 1 °C s8 5 80 15
Own curve, heating P5 MODBUS_HOLDING_REGISTER 41 1 °C s8 5 80 26
Own curve, heating P4 MODBUS_HOLDING_REGISTER 42 1 °C s8 5 80 32
Own curve, heating P3 MODBUS_HOLDING_REGISTER 43 1 °C s8 5 80 35
Own curve, heating P2 MODBUS_HOLDING_REGISTER 44 1 °C s8 5 80 40
Own curve, heating P1 MODBUS_HOLDING_REGISTER 45 1 °C s8 5 80 45
Point offset outdoor temperature MODBUS_HOLDING_REGISTER 46 1 °C s8 -40 30 0
Point offset MODBUS_HOLDING_REGISTER 47 1 °C s8 -10 10 0
External adjustment climate system 3 MODBUS_HOLDING_REGISTER 49 1 s8 -10 10 0
External adjustment climate system 2 MODBUS_HOLDING_REGISTER 50 1 s8 -10 10 0
External adjustment climate system 1 MODBUS_HOLDING_REGISTER 51 1 s8 -10 10 0
External adjustment with room sensor climate system 3 MODBUS_HOLDING_REGISTER 53 10 °C s16 50 300 200
External adjustment with room sensor climate system 2 MODBUS_HOLDING_REGISTER 54 10 °C s16 50 300 200
External adjustment with room sensor climate system 1 MODBUS_HOLDING_REGISTER 55 10 °C s16 50 300 200
Hot water demand mode MODBUS_HOLDING_REGISTER 56 1 s8 0 4 1
Start temperature HW high temperature MODBUS_HOLDING_REGISTER 58 10 °C s16 50 700 490
Start temperature HW normal temperature MODBUS_HOLDING_REGISTER 59 10 °C s16 50 600 460
Start temperature HW low temperature MODBUS_HOLDING_REGISTER 60 10 °C s16 50 550 420
Stop temperature HW periodic increase MODBUS_HOLDING_REGISTER 61 10 °C s16 550 700 550
Stop temperature HW high temperature MODBUS_HOLDING_REGISTER 62 10 °C s16 50 700 530
Stop temperature HW normal temperature MODBUS_HOLDING_REGISTER 63 10 °C s16 50 650 500
Stop temperature HW low temperature MODBUS_HOLDING_REGISTER 64 10 °C s16 50 600 480
Periodic hot water MODBUS_HOLDING_REGISTER 65 1 s8 0 1 1
Periodic hot water interval MODBUS_HOLDING_REGISTER 66 1 days s8 1 90 7
Start time periodic hot water MODBUS_HOLDING_REGISTER 67 1 - - - -
Hot water circulation MODBUS_HOLDING_REGISTER 2754 1 u8 0 1 0
Language MODBUS_HOLDING_REGISTER 91 1 s8 0 24 0
Period time hot water MODBUS_HOLDING_REGISTER 92 1 min u8 0 180 30
Period time heating MODBUS_HOLDING_REGISTER 93 1 min u8 0 180 30
Operating mode MODBUS_HOLDING_REGISTER 2743 1 u8 0 2 0
Operating mode heating medium pump MODBUS_HOLDING_REGISTER 95 1 u8 10 40 40
Operating mode brine pump MODBUS_HOLDING_REGISTER 96 1 u8 10 30 10
Activate forced control MODBUS_HOLDING_REGISTER 5000 1 u8 0 0 0
Max. internal additional heat MODBUS_HOLDING_REGISTER 102 100 kW s16 0 4500 700
Fuse MODBUS_HOLDING_REGISTER 103 1 A u16 1 400 16
Phase Order L3 MODBUS_HOLDING_REGISTER 2747 1 u8 1 128 4
Phase Order L2 MODBUS_HOLDING_REGISTER 2746 1 u8 1 128 2
Phase Orde